AF-ELEC-03high confidenceCritical
One electrode configuration used for every bus
All of the roughly 90 rows in the incident energy report use the VCB electrode configuration. The facility includes switchboards, transfer switches, UPS modules, PDUs and 208 V panelboards, which do not share one electrode arrangement. The uniform value is likely an unrevised software default.
- Source
- Source: Appendix F, Incident Energy Report, Electrode Config column
- Code ref
- not available (reported as a general engineering observation)
- Action
- Assign electrode configuration per bus from the actual equipment and re-run.
Electrode configuration is a direct input to incident energy, so this one column affects every result in the study.
AF-RES-01high confidenceCritical
Arcing current higher than bolted fault current at one bus
One 0.23 kV row reports 0.491 kA bolted and 0.533 kA arcing. Arcing current cannot exceed bolted fault current at the same bus. The next row reports 1.694 kA bolted and 1.259 kA arcing, the expected order, so the error appears limited to this row. Its result is 2.6 cal/cm² with a 31.2 in boundary.
- Source
- Source: Attachment A, Incident Energy Tabulation
- Code ref
- not available (reported as a general engineering observation)
- Action
- Re-derive the row. The incident energy and boundary for that bus follow from it.
The study was sealed and issued with this row, and the label for that equipment was printed from it.
AF-MODEL-01high confidenceCritical
IEEE 1584 edition and short-circuit method not stated
The report does not name the arc flash model, the IEEE 1584 edition, or the short-circuit method behind its results. Without them, the inputs the study had to declare and the applicability limits that apply cannot be determined.
- Source
- Source: methodology narrative; assumptions list; software settings appendix
- Code ref
- not available (reported as a general engineering observation)
- Action
- Ask the study author to state the model and IEEE 1584 edition, the short-circuit method, and the software and version used.
Every other check in a study review depends on these two statements.
AF-TIME-03high confidenceCritical
A 37-second trip time capped at a 2-second arc time
Two 0.23 kV rows report trip times of 36.842 s and 6.713 s, with the arc time capped at 2 s. The cap assumes a worker can move away within 2 seconds, and the work positions are inside wind turbines, where egress is limited.
- Source
- Source: §4 Basis of Analysis; Attachment A, low-voltage rows
- Code ref
- not available (reported as a general engineering observation)
- Action
- Evaluate egress at these work positions. If a worker cannot leave within 2 seconds, use the uncapped result.
The 2-second cap is the largest single assumption in that study.
AF-RES-04high confidenceCritical
Executive summary omits one of four buses above 40 cal/cm²
The summary names three locations above 40 cal/cm². The results table shows four (99.6, 72.4, 71.3 and 60.8 cal/cm²), and the 71.3 cal/cm² bus, the third highest, is not mentioned in the summary.
- Source
- Source: §1.3.3 Arc Flash Results; Appendix C Arc Flash Evaluation table
- Code ref
- not available (reported as a general engineering observation)
- Action
- Correct the summary to name all four buses and state how the omitted one is handled.
An omission in the summary can carry into the operation and maintenance (O&M) manual and then into a work permit.
AF-GEOM-03high confidenceCritical
No working distance in any results table
None of the results tables gives a working distance. Incident energy without its working distance cannot be compared to a PPE arc rating or transferred to a label.
- Source
- Source: §10 Attachments 6–9, results tables
- Code ref
- not available (reported as a general engineering observation)
- Action
- Add working distance to every row of the results tables.
The narrative says the labels carry working distance; the calculation output does not.